The requirements and tolerances permitted by this document are related to testing of a type test sample submitted for that purpose. Compliance of the type test sample does not ensure compliance of the whole production of a manufacturer. Compliance for production i the responsibility of the manufacturer and may include routine tests and quality assurance in
addition to type testing.
Except where otherwise specified in the sections of this document or relevant part of IEC 60598-2, luminaires shall be tested as delivered, and installed as for normal use, in an ambient temperature of between 10 °C and 30 °C,having regard to the manufacturer’s installation instructions. The lamp (or lamps) is (are) not included except where essential for
the test.
Luminaires cannot be regarded as meeting the requirements of this document unless all internal wiring is complete.
In general, the tests are made on a single sample luminaire or, where a range of similar luminaires is involved, on a single luminaire of each rated wattage in the range or on a representative selection from the range as agreed with the manufacturer (ee Annex S). This selection shall include the luminaire, together with any attachments, which represents the most unfavourable combination from a testing point of view.